When using a plate heat exchanger, when the flow of cold and heat medium is relatively large, the following methods can be used to reduce the resistance of the plate heat exchanger.


cooling water cooler factory- GUPHE

 

1. Adopt multi-process combination


When the flow rate of the cold and heat medium is large, a combination of multiple processes can be used, and more processes are used on the side of the small flow rate to increase the flow rate and obtain a higher heat transfer coefficient. A smaller process is used on the large flow side to reduce the resistance of the heat exchanger. Mixed flow patterns appear in the combination of multiple processes, and the average heat transfer temperature difference is slightly lower. Both the fixed end plate and the movable end plate of the plate heat exchanger adopting multi-process combination take over, which requires a lot of work during maintenance.


2. Adopt asymmetrical plate heat exchanger


The symmetrical plate heat exchanger is composed of plates with the same corrugated geometry on both sides of the plate, forming a plate heat exchanger with equal cross-sectional areas of the cold and hot runners. According to the heat transfer characteristics and pressure drop requirements of the cold and hot fluids, the asymmetric plate heat exchanger changes the waveforms of the two sides of the plate to form a plate heat exchanger with different cross-sectional areas of the cold and hot runners. The corner diameter is larger. The heat transfer coefficient of the asymmetrical plate heat exchanger decreases slightly, and the pressure drop is greatly reduced. When the flow of the cold and heat medium is relatively large, the use of an asymmetric single-process heat exchanger can reduce the plate area by 15%-30% compared to a symmetrical single-process heat exchanger.


3. Set the bypass pipe of the heat exchanger


 When the flow of cold and heat medium is relatively large, a bypass pipe can be set between the outlet of the heat exchanger on the side of the large flow to reduce the flow into the heat exchanger and reduce the resistance. In order to facilitate adjustment, a regulating valve should be installed on the bypass pipe. This method should adopt a countercurrent arrangement to make the temperature of the cold medium exiting the heat exchanger higher, and to ensure that the temperature of the cold medium after the confluence of the heat exchanger outlet can meet the design requirements. The bypass pipe of the heat exchanger can ensure that the heat exchanger has a higher heat transfer coefficient and reduce the resistance of the heat exchanger, but the adjustment is slightly more complicated.